| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | Fire extinguisher in machine room is expired. Replace or service, as needed. | 10/9/2025 | ||
| A17.1-1996 : Elevators | 1.8 - Door closing force | 112.4(b) | x | Car door closing force is over the maximum allowable of 30lbs, readjust closing force. | 10/21/2025 | |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | x | OSV is not sealed. Perform OSV test within 90 days, tag and seal upon completion. | 6/8/2022 |