Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.11.1 Yes No Car Floor to car sill has a 1/2" lip and presents a trip hazard. Bevel or level to removed trip hazard.
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.11.1 Yes No Hall Sill to hall floor presents a trip hazard on floors M, 2, 4, 6, 9, 20, 11, 12. Hall floor shall be level with hall sill.
A17.1-2016 : Elevators 11.1 - Access to Machine Room/Machinery Space/Control Room/Control Space 2.7.3 Yes No Machine Room and Secondary Machine room shall have a self closing and self locking door
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 Yes No Old and unused wiring and light switches in machine room shall be removed.
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space Yes No Machine room needs cleaned of construction dust and debris.
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 Yes No Air conditioning shall be installed and function to keep controllers at manufacturers recommended temperature.
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No Hostway shall be encolsed with a 2 hr fire rated construction throughout. Penetrations exist throughout hoistway and shall be patched and rated.
A17.1-2016 : Elevators 3.27 - Crosshead Data Plate and Rope Data Tags 2.20.2 Yes No Crosshead data plate shall be provided and engraved
A17.1-2016 : Elevators 4.12 - Standby power selection switch 2.27.2 Yes No Emergency Power / Standby power shall be tested
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Yes No Pit and Car top need cleaned of construction dust and debris.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph Yes No "In Case of Fire" signage shall be provided in hallway at each landing
A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 2.27.3 Yes Yes Fire alarm initiating device (smoke) on second floor shall recall elevator to main fire floor (floor 1)