A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
Yes
|
No
|
Car Floor to car sill has a 1/2" lip and presents a trip hazard. Bevel or level to removed trip hazard.
|
|
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
Yes
|
No
|
Hall Sill to hall floor presents a trip hazard on floors M, 2, 4, 6, 9, 20, 11, 12. Hall floor shall be level with hall sill.
|
|
|
A17.1-2016 : Elevators
|
11.1 - Access to Machine Room/Machinery Space/Control Room/Control Space
|
2.7.3
|
Yes
|
No
|
Machine Room and Secondary Machine room shall have a self closing and self locking door
|
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
Yes
|
No
|
Old and unused wiring and light switches in machine room shall be removed.
|
|
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Room and Machinery Space
|
Yes
|
No
|
Machine room needs cleaned of construction dust and debris.
|
|
|
A17.1-2016 : Elevators
|
2.6 - Ventilation
|
2.7.9.2
|
Yes
|
No
|
Air conditioning shall be installed and function to keep controllers at manufacturers recommended temperature.
|
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
Yes
|
No
|
Hostway shall be encolsed with a 2 hr fire rated construction throughout. Penetrations exist throughout hoistway and shall be patched and rated.
|
|
|
A17.1-2016 : Elevators
|
3.27 - Crosshead Data Plate and Rope Data Tags
|
2.20.2
|
Yes
|
No
|
Crosshead data plate shall be provided and engraved
|
|
|
A17.1-2016 : Elevators
|
4.12 - Standby power selection switch
|
2.27.2
|
Yes
|
No
|
Emergency Power / Standby power shall be tested
|
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
Yes
|
No
|
Pit and Car top need cleaned of construction dust and debris.
|
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.9 Elevator Corridor Call Station Pictograph
|
Yes
|
No
|
"In Case of Fire" signage shall be provided in hallway at each landing
|
|
|
A17.1-2016 : Elevators
|
6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators
|
2.27.3
|
Yes
|
Yes
|
Fire alarm initiating device (smoke) on second floor shall recall elevator to main fire floor (floor 1)
|
|