Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work, Re-inspection required 2/17/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher needs to serviced
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Hoistway doors need to be numbered on hoistway side. Not all are numbered.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No OSV shall be tested with full load. Tagged & sealed after satisfactory test. Re-inspection required
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned of water & debris. Place cover on sump pump. Re-inspection required
MO Minimum : Elevators (I) - Pits (I)8 No No Pit sump is missing cover.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No Replace missing/damaged pickup rollers, 3rd floor.
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 No No 4x4 electrical box in machine room needs to have wiring inside box and cover installed.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No Cab lighting - All lamps shall work.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a Yes No Clean pit of water and debris. 1/28/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall work. 1/31/2022
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No Fire extinguisher needs to be serviced.
A17.1-1996 : Elevators 4.2 - Hoistway doors 110 No No Hoistway doors shall be self-closing. 4th floor door jams.
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) No No Non-elevator related items shall not be stored in machine room.
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 1001.2(c)(15) No No Number the back of hoistway doors.
A17.1-1996 : Elevators 2.6 - Ventilation 102.4 No No Provide machine room ventilation to meet OEM temperature/humidity requirements. HVAC is not working.