A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.1
|
|
|
4x4 electrical box in machine room needs to have wiring inside box and cover installed.
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Cab lighting - All lamps shall work.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
|
Clean pit of water and debris.
|
1/28/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work, Re-inspection required
|
2/17/2025
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work.
|
1/31/2022
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Fire extinguisher needs to be serviced.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher needs to serviced
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Hoistway doors need to be numbered on hoistway side. Not all are numbered.
|
|
A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
110
|
|
|
Hoistway doors shall be self-closing. 4th floor door jams.
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2b (Clean Machine Room)
|
|
|
Non-elevator related items shall not be stored in machine room.
|
|
A17.1-1996 : Elevators
|
3.9 - Floor and emergency identification numbering
|
1001.2(c)(15)
|
|
|
Number the back of hoistway doors.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV shall be tested with full load. Tagged & sealed after satisfactory test. Re-inspection required
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned of water & debris. Place cover on sump pump. Re-inspection required
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Pit sump is missing cover.
|
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
102.4
|
|
|
Provide machine room ventilation to meet OEM temperature/humidity requirements. HVAC is not working.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Replace missing/damaged pickup rollers, 3rd floor.
|
|