MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work, Re-inspection required
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher needs to be serviced
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Place cover on sump pump
|
|
A17.1-1996 : Elevators
|
1.4 - Sills and car floor
|
204.2(a) Material for Car Enclosure Linings, and floor Coverings.
|
|
|
Cab flooring loose, needs to be refastened.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Red Tag)
|
x
|
x
|
Emergency phone not working.
|
1/28/2020
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Fire extinguisher needs to be serviced.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
210.2(g)
|
x
|
|
Repair pit light.
|
1/28/2020
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
x
|
|
Sump cover required to cover sump hole.
|
1/28/2020
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
x
|
Water and oil in pit causing damaged to pit equipment. Red tagged elevator.
|
8/24/2021
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
x
|
x
|
Audible signal for fireman's recall shall work.
|
8/24/2021
|