Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No The Phase 1 fire service key switch in the lobby is not readable. 8/4/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Test emergency power operation to complete the Cat 1 testing 3/10/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Test emergency power operation to complete the Cat 1 testing. Re-inspection required
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 5/23/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No The in car emergency lighting shall be operational. 5/23/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency bell shall be operational. 5/23/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.3.2.2 Cylinders Test shall be performed Yes No Cat 5 Test is incomplete, need to perform the following tests to complete: Setting of safeties with rated load, 125% brake test, pull out & pull thru & spinning of governor. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unit has emergency generator backup power, which needs to be scheduled and tested to complete inspection. Re-inspection required 8/27/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No The pit shall be kept clean. Clean the pit. 8/4/2023