Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Seal penetrations through hoistway sheetrock enclosure. 8/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 x Machine room lighting insufficient. Shall be 19 fc minimum at the floor level. 8/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Remove EMT raceways not related to the elevator operation from inside the hoistway 8/11/2020