Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.33 - Tanks 1004.2(b)(16) No No Tank that houses submersible hydraulic machine leaks oil on machine room floor through a crack in the tank. Tank needs to be repaired or replaced 2/22/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display current state operating certificate inside the machine 4/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation No No Test and log firefighter operation monthly 4/7/2022
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 211.9 No No Identify crosshead as Elevator #2 4/7/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No Post firefighter operating instructions on car operating panel 4/7/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No No No 2022 maintenance record log 11/26/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No emergency phone does not operate 11/27/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No CAR EMERGENCY PHONE NOT WORKING WHEN MAIN POWER TO THE ELEVATOR IS OFF 11/26/2025