Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(j) Out of date 5/12/2021
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Have the fire extinguisher re-certified it expired in 2022.
A17.1-1996 : Elevators 2.4 - Machine space 101.1a Provide a fire damper on the new HVAC added in the machine room
A17.1-1996 : Elevators 2.4 - Machine space 101.1a Fire caulk around the pipes entering the machine room.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must make emergency phone operable. 8.6.4.15 7/24/2024
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Re-install the light tubes in the car ceiling
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.11.2.1.1(r) x Must make car door restrictor operable. 7/5/2022