Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Car alarm bell shall work. 6/1/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 There is a hole in the car enclosure that shall be repaired.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The car lighting shall be repaired.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Each passenger car shall have lighting inside the enclosure of not less than five (5) foot-candles. Lighting shall be guarded to prevent breakage.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested and tagged, ABC type fire extinguisher, shall be provided in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Up-to-date wiring diagram shall be provided.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Car call buttons for the 2nd and 7th floors do not work.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars The top of the car shall be cleaned and rust removed.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Provide adequate machine room lighting.
MO Minimum : Elevators (H) - Machine Rooms (H)4 The machine room shall be kept clean.
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. Remove the rodents from the pit.
MO Minimum : Elevators (S) - Fire Service (S)1 x x The elevator was stuck on fire service and was unable to be returned to normal operation. Elevator Red-Tagged.
A17.1-2016 : Elevators 1.1 - Door Reopening Device 8.6.4.13.1(c) x The photo electric door re-opening device is not functional. Elevator Red-Tagged.