Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Re-inspection of battery lowering rescue unit. Upon removal of mainline power, car automatically returned to bottom landing without the use of a jumper. Auxiliary contacts may be wired incorrectly or needs additional set of contacts & wiring to prevent elevator from automatically lowering when mainline power is removed. Also, door would not open to let passengers out of the elevator. Re-inspection required 11/14/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide existing battery backup unit to work. 2/15/2023
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed, needs to be tested within 90 days 2/1/2022