A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Re-inspection of battery lowering rescue unit. Upon removal of mainline power, car automatically returned to bottom landing without the use of a jumper. Auxiliary contacts may be wired incorrectly or needs additional set of contacts & wiring to prevent elevator from automatically lowering when mainline power is removed. Also, door would not open to let passengers out of the elevator. Re-inspection required
|
11/14/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide existing battery backup unit to work.
|
2/15/2023
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV is not sealed, needs to be tested within 90 days
|
2/1/2022
|