A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code Repair 120 volt GFCI receptacle in machine room. 7/9/2020
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV not sealed. Perform OSV test on or before next annual inspection. 3/31/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Drain lines from jack are going back into the tank. Has to go to collection container, not larger than 5 gallons, located in the pit.