Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Maintenance control program shall include procedures for tests and inspections on paper located on-site. 10/7/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/30/2024
MO Minimum : Elevators (H) - Machine Rooms (H)1 Machine space gate to be kept locked.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Fire service testing must be documented monthly. The forms are present in the MCP, but are blank.
A17.1-2016 : Elevators 3.9 - Floor and emergency identification numbering 8.10.2.2.3(o) Floor identification numbering shall all match. Floor LL door frame is missing an "L". Floor ML door frame is missing "M"
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in-car telephone shall be operational. There is a dial tone, the phone dials out, but is never answered. 11/8/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work. Phone dials, operator ansers, but mircophone is not working.
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x Rear car door restrictor shall work at all floors. Car doors shall be restricted thorughout the hoistway when outside the landing zone. Rear door restrictor is missing brackets, does not work below the to landing.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Rear door restrictor shall work 8/9/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x OSV is due for full load test and tripping speed checked. Re-inspection required 10/10/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary power lowering is not working. Re-inspection required 11/20/2023