MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Alarm bell shall work with loss of main 120v power. Does not work with or withour power.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The in-car telephone shall be operational. There is a dial tone with a great deal of static. The phone apparently tries to dial out, but is never answered. This shall be corrected within 14 days.
|
11/21/2024
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
12/30/2024
|
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.10.2.2.1(r)
|
Yes
|
No
|
Rear car door restrictor shall work at all floors. Car doors shall be restricted thorughout the hoistway when outside the landing zone. Rear restrictor is missing brackets, does not work below top landing.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
Maintenance control program shall include procedures for tests and inspections and in paper located on-site.
|
10/7/2020
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
No
|
No
|
Fire service testing must be documented monthly. The forms are in the MCP, but are blank.
|
|