Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. 10/26/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 2-way communication decive shall work. Does not work without 110v. Also operator stated call is very faint.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records x Up to date wiring diagrams shall be provided and permanently kept in the machine room. Re-inspection to enforce.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Maintenance control program shall include procedures for tests and inspections on paper located on-site. 10/7/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. There were no diagrams in the machine room at the time of the inspection. 12/30/2024
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean and dry. 10/7/2020
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.19.15 Emergency Communications x Emergency light shall work. Only 1 lamp is working.
A17.1-2016 : Elevators 3.2 - Car top light and outlet 8.10.2.2.3(b) Cartop shall have lamp and guard.