A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
8.10.2.2.3(b)
|
|
|
Cartop shall have lamp and guard.
|
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.19.15 Emergency Communications
|
x
|
|
Emergency light shall work. Only 1 lamp is working.
|
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication decive shall work. Does not work without 110v. Also operator stated call is very faint.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Maintenance control program shall include procedures for tests and inspections on paper located on-site.
|
10/7/2020
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean and dry.
|
10/7/2020
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers.
|
10/26/2018
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
x
|
|
Up to date wiring diagrams shall be provided and permanently kept in the machine room. Re-inspection to enforce.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams
|
|
|
Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. There were no diagrams in the machine room at the time of the inspection.
|
12/30/2024
|