Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures The “Fireman’s Service Phase I” signage is not located at the primary landing adjacent to the Fireman’s Service Phase I key switch as required. Reinstall signage to comply with ASME A17.1 2004a.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph The pictograph signage for “In Case of Fire” is missing at multiple elevator landings. Reinstall signage that conforms to the ASME A17.1 2004a that this elevator was designed to conform to.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The “smoke guard” barrier device, that is installed on the bottom hoistway door landing, has been activated and not reset properly. The device has been temporarily held up by a ladder rendering it inoperable in case of an actual emergency. Repair and reset the“smoke guard” barrier device to operate as designed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.11.2.1.1(e) Car Lighting Multiple car light fixtures in the car are not operational and shall be repaired to provide adequate lighting inside the elevator car.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair this device to operate as required in A17.1 2004a 3.26.10. 9/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 9/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work on 110v emergency power or normal power. 1/7/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 x Car does not access all floors on phase 2