Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) x Emergency lowering device not working 11/20/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. 10/26/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The emergency light fixture inside the elevator is not operational and shall be repaired. 10/26/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. 7/23/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. 7/23/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The slack rope switches in the pit fail to activate when the elevator safeties are set and the hoist rope becomes slack. Slack rope switches shall be adjusted to operate as designed 9/17/2019
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)5 x x The slack rope switches in the pit fail to activate when the elevator safeties are set and the hoist rope becomes slack. Slack rope switches shall be adjusted to operate as designed 9/3/2020