Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Adjust upthrust roller bearings for proper clearance to door hangar track (multiple floors). 8/29/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall work. Take corrective action as needed. 5/13/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.1.7 x 8.6.1.7.5 - The auxiliary power lowering operation shall be functional. 10/18/2021
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x The auxiliary power lowering operation shall be functional. 12/2/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall be operational. The phone dials out then hangs up. 9/6/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. Note: This switch must be present for auxiliary lowering to function. 12/2/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 12/2/2022
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. 12/2/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 12/2/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Trips to location are not being properly documented. 8/29/2023
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) Clean the car top 8/29/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/2/2022