Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed 9/12/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed in the control space. 9/12/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No DOOR CLOSE BUTTON IS LABELED #1 9/12/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No Post firefighter instructions next to hall firefighter keyswitch 9/12/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No Pit access door needs to be self-locking 9/12/2024
A17.1-1996 : Elevators 3.26 - Broken rope, chain, or tape switch 1001.2(c)(9) Yes No Slack belt switch does not function. 8/13/2021
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.2 No No Install heat detector within 24 inches from each machine room sprinkler 9/12/2024
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No Provide tye ABC fire extinguisher inside control room near access door 7/29/2019
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 8.6.4.20.11 (Re-Inspection) Yes No Perform unintended motion and ascending car protection tests 8/22/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Test and log firefighter operation monthly 8/24/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Test and log firefighter operation monthly 8/24/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No No MCP 9/12/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No No No maintenance records on site 9/12/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(b)(5) No No Written procedures for tests and inspections need to be kept in the control room. 9/12/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No No maintenance control plan on site 9/12/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No No No maintenance records on site 9/12/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(b)(5) No No Keep written procedures for tests and inspections on site 9/12/2024
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 8.6.4.20.1 Yes No Perform full load safety test 8/22/2023
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 8.6.4.19.2 Yes Yes Perform annual no load safety test 8/21/2023
A17.1-1996 : Elevators 2.1 - Access to machine space 101.1a No No HOLE IN MACHINE ROOM CELING NEEDS TO BE PATCHED AND FIRE RATED 9/12/2024
A17.1-1996 : Elevators 1.7 - Car door or gate 204.4 No No CAR DOOR GAP IS >1/2" . NEEDS TO BE ADJUSTED 9/12/2024
A17.1-1996 : Elevators 1.7 - Car door or gate 204.6 No No DOOR GAP IS >1/2'' 6/27/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not operate 7/2/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No PROVIDE WORKING PHONE
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not operate 7/26/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not operate 8/22/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No SUPPLY WORKING LIGHT AND BELL 4/29/2026
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) No No Replace broken bezel identification marking for firefighter keyswitch 8/24/2021
A17.1-1996 : Elevators 1.12 - Car enclosure 204 No No Replace missing car direction lantern fixture in car enclosure opening. 9/12/2024
A17.1-1996 : Elevators 1.12 - Car enclosure 204 No No Replace missing car direction lantern fixture in the car enclosure 9/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Post In Case of Fire signage next to hall button fixture at each landing 9/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Post In Case of Fire signage next to hall button fixture at each landing 9/12/2024