A17.1-1996 : Elevators
|
5.11 Plunger and Cylinder
|
1206.5b(5) Oil Leakage Collection
|
|
|
Must provide means to monitor oil loss from Jack Packing. (currently overflow tube are routed back to Power unit with no monitoring)
|
1/18/2024
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Must provide all required MCP (maintenance control program documents and logs. 8.6.1.2.1
|
1/18/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone failed to operate.
|
5/31/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Must make emergency Phone Operable. 8.6.4.15
|
3/1/2024
|