Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.1 Escalator Handrails Right handrail is cracked, needs to be replaced
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x Demarcation light missing on top landing 6/12/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x Upper demarcation lights not working.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.11.4.2.13 Escalator Handrail Safety Systems x Provide testing of the escalator handrail speed sensor.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.3 Step/Skirt Performance Index x Provide testing, record results.
A17.1-1996 : Escalators 8.12 - Steps, step chains, and trusses 802.7 x Step chains are bad and need to be replaced. Steps do not mesh with each other. Red-tagged 12/23/2021