MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/8/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
3/8/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)6
|
|
|
Machines, motors, and disconnects shall be conspicuously marked.
|
3/8/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
Make repairs to the 2nd and 4th floor landing doors for proper operation and alignment.
|
3/28/2019
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)5
|
|
|
Pull straps shall be installed on all hoistway doors.
|
3/8/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)11
|
|
|
Replace the basement landing door rope.
|
3/28/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The pit light shall work.
|
3/28/2019
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
The top panel of the fourth floor hoistway door is not hanging level, resulting in a 4" gap. It shall be re-hung and/or repaired.
|
3/8/2022
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)2
|
|
|
Wire ropes on drum-type machines shall be re-socketed once a year.
|
3/8/2022
|