Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 3/8/2022
MO Minimum : Elevators (H) - Machine Rooms (H)6 Machines, motors, and disconnects shall be conspicuously marked. 3/8/2022
MO Minimum : Elevators (A) - Hoistways (A)1 Make repairs to the 2nd and 4th floor landing doors for proper operation and alignment. 3/28/2019
MO Minimum : Elevators (A) - Hoistways (A)5 Pull straps shall be installed on all hoistway doors. 3/8/2022
MO Minimum : Elevators (A) - Hoistways (A)11 Replace the basement landing door rope. 3/28/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit light shall work. 3/28/2019
MO Minimum : Elevators (A) - Hoistways (A)1 The top panel of the fourth floor hoistway door is not hanging level, resulting in a 4" gap. It shall be re-hung and/or repaired. 3/8/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)2 Wire ropes on drum-type machines shall be re-socketed once a year. 3/8/2022