MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service test and post a log in the machine room
|
7/21/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
|
7/14/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the elevator pit, there is an oil and water mixture on the pit floor.
|
7/14/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
replace the emergency light battery, it is dead.
|
8/17/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces
|
|
|
repair/replace sheetrock for the machine room wall that was removed to repair water lines in the wall.
|
7/14/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
finish cleaning the pit, pig mat is not to be left on the pit floor
|
5/18/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate in the machine room is to be updated every year
|
5/18/2022
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
recovery pump in the elevator pit is not allowed per state of Missouri memo 006, replace with a bucket
|
10/26/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
standing oil on the pit floor, clean the pit
|
10/26/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
repair the pickup rollers assemblies on both landings, on the bottom landing the stop bolt is bent and on the top landing the stop bolt is sheared off
|
10/26/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Recovery pump in the elevator pit not allowed per memo from the state, memo 006 A17.1 8.6.5.5
|
10/24/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Standing oil on pit floor, clean the pit, replace leaking Victaulic couplings
|
10/24/2024
|