Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is sealed and tagged (4/27/22) but test (performed by a different maintenance and inspection company) was not submitted to the State of Missouri properly. Test documentation shall be submitted to the state to properly update database with date of last 5 year. If testing was not completed, it is due now.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Fire service testing must be documented monthly.
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed. Perform test on or before next annual inspection date. 1/13/2022
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed as noted on last inspection, Re-inspection required 4/27/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the state operating certificate shall be displayed in the machine room 10/20/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state certificate shall be displayed in the machine room 10/20/2023