Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems The hoistway doors at a number of landings are not self-closing. The hoistway doors shall be adjusted.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems The hoistway door at the top landing is missing a door retaining gib.. The door retaining gib shall be reinstalled.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems The front door operator cover has been removed, reinstall cover to prevent accidental contact by maintenance and emergency personnel.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems The hoistway door interlock cover is missing, reinstall cover to prevent accidental contact by maintenance and emergency personnel.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency light does not work. 12/8/2020
A17.1-1996 : Elevators 2.35 - Supply Line and Shutoff Valve 303 Remove temporary wood pit supply line supports and firmly anchor line to floor with noncombustable supports. 1/6/2021
A17.1-1996 : Elevators 3.2 - Car top light and outlet 204.7 Replace car top light and guard. 1/6/2021
A17.1-1996 : Elevators 6.3 - Firefighters' service (A17.1-1984 through A17.1a-1988 and A17.3) 112.3d x x Phase II fire service to work per the code. Did NOT red tag elevator. 9/10/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x 211.3(b)(5) The “bypass” operation is not operational and is only resetting the elevator phase I operation. Reinitiate “bypass” operation to operate to the correct version of fire service this elevator is installed to. 6/13/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x 211.3(b)(5) The “bypass” operation is not operational and is only resetting the elevator phase I operation. Reinitiate “bypass” operation to operate to the correct version of fire service this elevator is installed to. This shall be corrected and reinspected within 30 days or the elevator shall be removed from service until repaired.