Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.35 - Supply Line and Shutoff Valve 303 No No Remove temporary wood pit supply line supports and firmly anchor line to floor with noncombustable supports. 1/6/2021
A17.1-1996 : Elevators 3.2 - Car top light and outlet 204.7 No No Replace car top light and guard. 1/6/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate shall be displayed in elevator Machine room. 5/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No The front door operator cover has been removed, reinstall cover to prevent accidental contact by maintenance and emergency personnel. 5/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No The hoistway door at the top landing is missing a door retaining gib.. The door retaining gib shall be reinstalled. 5/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No The hoistway door interlock cover is missing, reinstall cover to prevent accidental contact by maintenance and emergency personnel. 5/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No The hoistway doors at a number of landings are not self-closing. The hoistway doors shall be adjusted. 5/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. 5/18/2026
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f Yes No 211.3(b)(5) The “bypass” operation is not operational and is only resetting the elevator phase I operation. Reinitiate “bypass” operation to operate to the correct version of fire service this elevator is installed to. 6/13/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f Yes No 211.3(b)(5) The “bypass” operation is not operational and is only resetting the elevator phase I operation. Reinitiate “bypass” operation to operate to the correct version of fire service this elevator is installed to. This shall be corrected and reinspected within 30 days or the elevator shall be removed from service until repaired. 5/7/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency light does not work. 12/8/2020
A17.1-1996 : Elevators 6.3 - Firefighters' service (A17.1-1984 through A17.1a-1988 and A17.3) 112.3d Yes Yes Phase II fire service to work per the code. Did NOT red tag elevator. 9/10/2019