Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Remove water from pit. 12/18/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 8.11.2.1.1(d) The car flooring has become de-attached at a number of locations resulting in a potential tripping hazard to passengers. Repair the flooring to minimize the risk of of the tripping hazard. 9/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator alarm bell button inside the elevator is not working. Check and repair the alarm bell button for proper operation and passenger safety. Reinspection required. 9/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures The “Fireman’s Service Phase I” signage is not located at the primary landing adjacent to the Fireman’s Service Phase I key switch as required. Reinstall signage to comply with ASME A17.1 2004. 9/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph The pictograph signage for “In Case of Fire” is missing at multiple elevator landings. Reinstall signage that conforms to the ASME A17.1 2004a that this elevator was designed to conform to. 9/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work on 110v emergency power or normal power.