MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Ceiling panels in car are open egg crate type design, providing no protection for passengers in event of bulb breakage. Replace panels with solid type, install plastic tubes and endcaps over bulbs or replace with LED type bulbs
|
5/18/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency two communication device does not operate. The shall be able to establish two way communication in case of intrapment. Repair and reinspect
|
8/13/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to have oil collection pans emptied and pit floor cleaned of oil
|
5/18/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
OSV is due for testing as noted in last inspection, Re-inspection required
|
9/14/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
3/13/2024
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the state certificate shall be displayed in machine room
|
5/18/2023
|