Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting shall be operational. 11/19/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Remove the abandoned electrical meter base in the machine room. 12/5/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant maintenance control program (MCP) will be required no later than January 1, 2022. 1/23/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 1/23/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors There are missing floor tiles inside the car. All passenger elevator car floors shall be maintained so that persons are not exposed to the hazards of tripping or falling. 7/27/2023
MO Minimum : Elevators (A) - Hoistways (A)16 Travel cable insulation damaged. Shall be properly repaired (not silver duct tape). 12/5/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No MCP is present in the machine room. A code compliant MCP shall be provided. 12/5/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing and self-locking. 12/5/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Remove the abandoned electrical meter base in the machine room. 12/5/2024
MO Minimum : Elevators (H) - Machine Rooms (H)8 4x4 electrical box in machine room needs to have wiring inside box and cover installed. 12/5/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 9/24/2024
conversion conversion conversion - reinspect x Emergency phone not operating. 7/26/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x In car emergency telephone shall be operational. 11/19/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work (with and without main power) and give proper location. The line is dead. 10/6/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x 8.6.1.7.5 - The emergency lowering device (ERU) shall be operational. 7/28/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The car top GFCI has an open ground. 7/28/2021