Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need maintenance control program on site and posted on controller 11/4/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service has to be tested monthly and recorded on log in machine room 11/4/2020
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x Car door restrictor does not work. 10/29/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work. 10/29/2021
A17.1-1996 : Elevators 2.32 - Control Valve 1004.2(b)(15) x Performed OSV test, elevator would not lift load due to control valve failure. Red tagged elevator. 10/29/2021
A17.1-1996 : Elevators 3.14 - Hoistway clearances 108 x Clearance between the 1st floor landing sill and elevator car sill is a 1/4 inch. Clearance shall be between 1/2 inch and 1 1/2 inches. Re-inspection required 10/10/2024
A17.1-1996 : Elevators 3.14 - Hoistway clearances 1001.2(c)(20) x Clearance between the 1st floor landing sill and elevator car sill is a 1/4 inch. Clearance shall be between a 1/2 inch and 1 1/2 inches.
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems x Safety retainers are missing on top and bottom hoistway doors, need to install safety retainers. Re-inspection required 10/10/2024
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems x Bottom floor hoistway door closing device does not work, needs repaired. Re-inspection required 10/10/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) Sump is full of oil and unplugged. 11/4/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Repair GFI receptable and light in pit. 11/4/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 x Door open button not working properly on Phase I recall. Reinspect 14 days to repair. Phase I recalls the elevator to main floor and opens door. Door open button will not reopen door once on Phase I. 7/2/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 11/4/2020