A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13 Door Systems
|
x
|
|
Bottom floor hoistway door closing device does not work, needs repaired. Re-inspection required
|
10/10/2024
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
Car door restrictor does not work.
|
10/29/2021
|
A17.1-1996 : Elevators
|
3.14 - Hoistway clearances
|
108
|
x
|
|
Clearance between the 1st floor landing sill and elevator car sill is a 1/4 inch. Clearance shall be between 1/2 inch and 1 1/2 inches. Re-inspection required
|
10/10/2024
|
A17.1-1996 : Elevators
|
3.14 - Hoistway clearances
|
1001.2(c)(20)
|
x
|
|
Clearance between the 1st floor landing sill and elevator car sill is a 1/4 inch. Clearance shall be between a 1/2 inch and 1 1/2 inches.
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
Door open button not working properly on Phase I recall. Reinspect 14 days to repair. Phase I recalls the elevator to main floor and opens door. Door open button will not reopen door once on Phase I.
|
7/2/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Fire service has to be tested monthly and recorded on log in machine room
|
11/4/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Need maintenance control program on site and posted on controller
|
11/4/2020
|
A17.1-1996 : Elevators
|
2.32 - Control Valve
|
1004.2(b)(15)
|
|
x
|
Performed OSV test, elevator would not lift load due to control valve failure. Red tagged elevator.
|
10/29/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work.
|
10/29/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State certificate in machine room
|
11/4/2020
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Repair GFI receptable and light in pit.
|
11/4/2020
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13 Door Systems
|
x
|
|
Safety retainers are missing on top and bottom hoistway doors, need to install safety retainers. Re-inspection required
|
10/10/2024
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Sump is full of oil and unplugged.
|
11/4/2020
|