Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x Phase 1 key switch does not operate, however phase 1 recall functions properly when smoke detectors are simulated. 9/3/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Both Phase I & II fire service key switches shall be same key. 10/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.7 - Car door or gate 8.11.2.1.1(g) Missing door gibs on hall doors 4,5,5M 10/26/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency light and alarm bell do not work. 12/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x Repair car door restrictor. 6/30/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Elevator cab emergency lights do not work. Re-inspection required 5/23/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Replace missing hoistway door gibbs on floors 1,4,5 & 5M. Re-inspection required 10/8/2024