Phase 2 fire service doors would not close.
|
9/3/2018
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
Yes
|
No
|
Car is not returning to the proper floor on Phase I fire service.
|
10/30/2019
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
Yes
|
No
|
Phase II is not working.
|
10/30/2019
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
Yes
|
No
|
On phase I & 2 fire service, the door re-opening device is not over-ridden, need to repair light ray. Re-inspection required
|
11/15/2022
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
No
|
No
|
Elevator pit light has an illumination of less than 5 foot candles. Pit light shall have not less than 5 foot candles at the pit floor
|
3/10/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
No
|
No
|
There shall be a written maintenance control program kept on site in the machine room
|
3/10/2026
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency light and bell shall be repaired.
|
6/30/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
Yes
|
No
|
Door closing force exceeds 30lbs. Shall be adjusted to less than 30 lbs.
|
6/30/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
Yes
|
No
|
Car running 35% greater than contract speed. OSV test could not be completed. Adjust valve to contract speed in the down director so OSV test can be completed. Pressure Relief test also needs to be completed.
|
6/30/2026
|