Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x Phase 2 fire service doors would not close. 9/3/2018
MO Minimum : Elevators (S) - Fire Service (S)1 x Car is not returning to the proper floor on Phase I fire service. 10/30/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase II is not working. 10/30/2019
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x On phase I & 2 fire service, the door re-opening device is not over-ridden, need to repair light ray. Re-inspection required 11/15/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Elevator pit light has an illumination of less than 5 foot candles. Pit light shall have not less than 5 foot candles at the pit floor
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation There shall be a written maintenance control program kept on site in the machine room