Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV installed and not sealed or tagged. Perform OSV test on or before next annual inspection.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Provide current year tested fire extinguisher in the elevator machine room.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h x Provide current year tested fire extinguisher in the elevator machine room.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) Clean the pit (oil).
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) x Cylinder packing(r) is worn and leaking, repair as needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean the car top.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Provide machine room door to be self closing and locking. (Currently pull and it is open)
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) x Cylinder packing (R) is worn and leaking. 3/21/2025