Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.36 - Hydraulic Cylinders 302.3 Cylinder packing (right piston) worn and leaking, repair as needed.
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required. 2nd notice 4/21/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 5/7/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) Fire extinguisher needs to be serviced. 2.7.1 6/11/2020
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 Main line disconnect has missing hardware on latch, presenting difficulty for lock out/tag out. Repair as needed, replace if necessary.
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not tagged or sealed. Perform test, tag and seal valve upon completion. 8/8/2022
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Provide machine room door to be self closing. Existing closer is broken/ damaged.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Remove oil from pit floor and sump. 6/11/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x Remove oil from pit floor and sump. 1/23/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair inoperative emergency phone. 1/23/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) Replace or service fire extinguisher.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication not working. 8/8/2022