Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Pit floor shall be kept dry and free of water 2/23/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x alarm bell not working 9/30/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Red Tag) x x 1.6 telephone does not work 5/2/2019
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) controllers need covers on at all times/if machine room is to hot steps need to be taken to correct issue 12/16/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits I-i pit needs to be dry and clean 12/16/2020
conversion conversion n/a water and oil in pit --needs to be cleaned out 12/16/2020
conversion conversion n/a needs current cedrtifivate posted in machine room 12/16/2020
conversion conversion n/a packing on jack needs to be replaced 12/16/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate current certificate needs posted 12/16/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate in machine room 2/23/2024