Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Replace fire extinguisher in machine room
conversion conversion n/a Observed most recent elevator certificate not framed in machine room. 7/20/2018
conversion conversion n/a Observed car emergency lighting not working. 7/20/2018
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. This violation was issued on the last annual inspection which would indicate that the battery charging system is not operating and shall be repaired. 5/16/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. This violation was issued on the last annual inspection which would indicate that the battery charging system is not operating and shall be repaired. 5/24/2019