A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. This violation was issued on the last annual inspection which would indicate that the battery charging system is not operating and shall be repaired.
|
5/24/2019
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. This violation was issued on the last annual inspection which would indicate that the battery charging system is not operating and shall be repaired.
|
5/16/2019
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Replace fire extinguisher in machine room
|
|
conversion
|
conversion
|
n/a
|
|
|
Observed most recent elevator certificate not framed in machine room.
|
7/20/2018
|
conversion
|
conversion
|
n/a
|
|
|
Observed car emergency lighting not working.
|
7/20/2018
|