Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Observed most recent elevator certificate not framed in machine room. 7/20/2018
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, and governor tested before the inspection is completed. 4/5/2021
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)8 x x Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that the mechanical and electrical protection devices would not activate within the required limits. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service. 4/5/2021