Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a low oil protection shall work 10/1/2024
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Low oil timer not working. 2.39 10/1/2024
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lights need to be repaired. 10/1/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 11/13/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Elevator must have a MCP kept in machine room for each unit 10/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A written copy of the MCP shall be kept in the machine room 11/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Door re-opening photo eyes do not work. Repair or replace same. Unit has working mechanical edge. Re-inspection required 10/14/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/1/2024