Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)16 All electrical wiring in the hoistway shall be enclosed in metal conduit, flexible conduit, or metal raceway to be in compliance with NFPA 70, National Electric Code. The first landing hoistway door interlock is missing its cover and shall be replaced. 4/19/2019
MO Minimum : Elevators (A) - Hoistways (A)16 Replace missing duct covers, wiring exposed at lower level. 3/1/2022
MO Minimum : Elevators (A) - Hoistways (A)16 Replace missing covers on duct at top of hoistway and on 1st floor interlock 12/30/2021
MO Minimum : Elevators (A) - Hoistways (A)16 x Remove non elevator related wiring from elevator pit 1/19/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)4 Replace missing gate handles and hand guards on car gate 12/30/2021
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)1 Each freight car shall have a solid enclosure of at least 6' in height. The space between the solid section and the top of car top shall be covered solid or with perforated or lattice-type work. The perforated or lattice work shall reject a ball 1.5" in diameter. Replace the missing panel. 4/19/2019
MO Minimum : Elevators (F) - Electrical Switches (F)2 x All electric elevators shall have upper and lower final limit switches. Elevator will not hit top final limit due to suspension rope stretching. The suspension ropes shall be shortened to allow testing of top final limit. 8/13/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The phase 1 & phase 2 fire service key switches shall be legible. 9/30/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The car top light shall be operational and shall be guarded. 9/30/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The machine room fire extinguisher is expired and shall be serviced or replaced. 9/30/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency phone does not work. 4/27/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Secure unlocked hoistway lock boxes, top and bottom. 3/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Repair inoperative emergency light 1/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Repalace broken door clutch assembly on basement door 1/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams Repair landing control stopping failures, car goes past landing it's called to stopping about halfway between that landing and the next landing. When called to the top landing it went past hitting hitting final and became stuck in the overhead.
MO Minimum : Elevators (H) - Machine Rooms (H)4 The machine room shall be kept clean. 9/30/2019
MO Minimum : Elevators (I) - Pits (I)1 The debris in the pit shall be removed. The pit shall be kept clean. 9/30/2019
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage x Phase 2 fire service shall be operational. 2/26/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 2 fire service does not work, and shall be repaired and tested. 8/13/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Cat 5 incomplete.. Provide governor PO/PT, record results. 1/8/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Cat 5 incomplete. Provide electrical switch and mechanical jaw of governor to be tested. Record results. 1/8/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Cat 5 incomplete. Provide 125% brake test. 1/8/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Cat 5 incomplete. Provide full load safety test., record slide. 1/8/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.3 Maintenance Personnel Maintenance, repairs, replacement , and test shall be performed only by elevator personnel.
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems x All landing and car -door or gate mechanical and electrical components shall be maintained to ensure safe and proper operation including but not limited to, the following: (a) hoistway door interlocks or mechanical locks and electric contacts, (b) car door electric contacts, (e) Hoistway door unlocking devices, (f) hangers, tracks, door rollers, and up-thrusts, (h) sills and bottom guides, fastenings, condition, and engagement. (k) door closers, where required.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate shall be displayed in machine room 12/30/2021