Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties Table 205.3 x x When setting the safeties, the car slide is only reaching 19”. The minimum slide for this car is 33”. Repair or replace as needed 4/4/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing was incomplete and must have the buffers compressed with weights to complete test. 4/4/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fire service shall be tested. Re-inspection required 10/4/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Shorten Hoist cables counter weights striking buffer when car is at top landing
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Repair phone so that it will operate in the event of a power outage 1/2/2024