MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Fire service shall be tested. Re-inspection required
|
10/4/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair phone so that it will operate in the event of a power outage
|
1/2/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
Shorten Hoist cables counter weights striking buffer when car is at top landing
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Testing was incomplete and must have the buffers compressed with weights to complete test.
|
4/4/2022
|
A17.1-1996 : Elevators
|
2.29 - Car and counterweight safeties
|
Table 205.3
|
x
|
x
|
When setting the safeties, the car slide is only reaching 19”. The minimum slide for this car is 33”. Repair or replace as needed
|
4/4/2022
|