MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
Yes
|
Yes
|
Elevator red tagged due to being 5 years past due inspection. Have elevator inspected, correct all violations and obtain a current state operating certigicate.
|
7/23/2026
|
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
No
|
No
|
Must provide and maintain Code Data Tag. 8.6.1.6.7
|
9/9/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
No
|
No
|
Must Provide Means to monitor Oil loss from jack packing Gland. 8.5.5.5.2
|
9/9/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
Must provide Annual test tag on Machine room Fire Extinguisher. 8.6.1.6.5
|
9/9/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.1 Means of Communication (Red Tag)
|
No
|
No
|
Repair the emergency phone as the incoming line is dead.
|
7/13/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Obtain and display a current state operating certificate in the machine room.
|
7/13/2026
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(b)(1)
|
No
|
No
|
Provide a copy of the MCP in the machine room.
|
7/13/2026
|