MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements A maintenance log shall be kept on-site. 10/7/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be a self-locking door. 10/7/2019
MO Minimum : Elevators (I) - Pits (I)1 There is standing water in the pit. The pit shall be kept clean and dry. Remove water from pit and correct source of leak. 7/25/2024
MO Minimum : Elevators (I) - Pits (I)3 Counterweight guards shall extend from a point not more than twelve inches (12") above the pit floor to a point not less than seven feet (7') above the pit floor. 11/22/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) A rope data tag is required on the governor rope and the hoist ropes. 10/7/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 11/22/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/22/2021