MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
A maintenance log shall be kept on-site.
|
10/7/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be a self-locking door.
|
10/7/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
There is standing water in the pit. The pit shall be kept clean and dry. Remove water from pit and correct source of leak.
|
7/25/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)3
|
|
|
Counterweight guards shall extend from a point not more than twelve inches (12") above the pit floor to a point not less than seven feet (7') above the pit floor.
|
11/22/2021
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)1(A)
|
|
|
A rope data tag is required on the governor rope and the hoist ropes.
|
10/7/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
11/22/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
11/22/2021
|