Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x emergency phone does not operate
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not provide two way conversation. Call connects to voicemail message. 8/17/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x Fire service phase 1 keyswitch needs to designate "ON-OFF-BYPASS" positions. No designation present and keyswitch spins around due to loose mounting. 10/3/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Identify the inside of hoistway doors with a numeral corresponding to the landing floor
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Identity inside of hoistway door with a numeral corresponding to the landing floor
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Install guarding over car light fixtures
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door needs to be self locking and non-defeatable
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys Need to provide firefighter key on site.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire signage at each landing next to hall call station
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Provide maintenance records of procedures per maintenance control plan.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Remove hydraulic oil from pit floor
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger pump from pit. Cylinder drain lines need to be ran to pit collection containers of no more than 5 gallon capacity.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replacement for identification marking on hall firefighter keyswitch needs to be of equivalent material and design as the original bezel. Handwritten marking on a piece of tape stuck on the wall does not meet this requirement.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly