MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Telephone in car doesn't work - Recording says "wrong extension" can not complete call
|
1/28/2021
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Standby power fails to lower elevator and open doors when normal power is removed
|
5/15/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load every 5 years.
|
6/13/2023
|