MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Fireman's emergency service shall be tested. Re-inspection required
|
10/4/2022
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1002.2g (Standby Power Operation)
|
x
|
|
Provide testing of the elevator on emergency power.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fireman's recall was not tested.
|
4/9/2021
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Fire service maintenance control program needs to be placed in machine room.
|
|
A17.1-1996 : Elevators
|
4.12 - Standby power selection switch
|
1001.2(d)(12)
|
x
|
|
Provide testing of the elevator emergency power selector switch.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|